高低压配电柜应该怎么摆放?
发布时间:2023-12-28来源://www.aqfitlab.com/浏览量:
1、配电柜的标高或笔直度超出答应偏差,是由于丈量定位不或者是地上凹凸不平形成的,应及时进行批改。
1. The elevation or straightness of the distribution cabinet exceeding the allowable deviation is due to poor measurement positioning or uneven ground, and should be corrected in a timely manner.
2、 配电柜在设备铁架之前未进行调直找正,或设备时固定点位置偏移形成的,运用吊线重新找正后再进行固定。
2. If the distribution cabinet is not straightened and aligned before the equipment iron frame, or if the fixed point position of the equipment is offset, use a suspension wire to re align and then fix it.
3、配电柜面电具、仪表不牢固、平允或距离不均,压头不牢、压头伤线芯,多股导线压头未装压线端子。闸具下方未装卡片框。不紧的应拧紧,距离应按要求高速均匀,找平整。伤线芯的部分应剪掉重接,多股线应装上压线端子,卡片框应补装。
3. The electrical appliances and instruments on the distribution cabinet surface are not firm, level or uneven in distance, the pressure head is not firm, the pressure head damages the wire core, and the pressure head of multiple wires is not equipped with pressure wire terminals. There is no card frame installed below the gate. The parts that are not tight should be tightened, and the distance should be high-speed and uniform according to the requirements, and the surface should be leveled. The damaged part of the wire core should be cut off and reconnected, multi stranded wires should be equipped with crimping terminals, and card frames should be repaired.
4、配电柜接地导线截面不够或维护地线截面不够,维护地线串接,对这些不符合要求的应按有关规定进行纠正。
4. The grounding wire section of the distribution cabinet is insufficient or the maintenance ground wire section is insufficient, and the maintenance ground wire is connected in series. Any non-compliance with these requirements should be corrected according to relevant regulations.
5、配电柜后配线摆放不整齐。应按支路绑扎成束,并固定在盘内。
5. The wiring behind the distribution cabinet is not neatly arranged. It should be tied into bundles according to the branch and fixed in the tray.
6、配电柜(盘)缺零部件,如合页、锁、螺丝等,应配齐各种设备所需零部件。
6. The distribution cabinet (panel) lacks components such as hinges, locks, screws, etc., and should be equipped with all necessary components for the equipment.
7、内壁粗糙木箱内部应修理平整,表里做处理,并应考虑措施。
7. The rough inner wall of the wooden box should be repaired and leveled, and the surface and interior should be treated, and measures should be considered.
8、配电柜内壁焊点锈蚀,应补刷防锈漆。铁柜不得用电(气)焊进行开孔,应采用开孔器进行开孔。
8. The welding points on the inner wall of the distribution cabinet are corroded and should be repainted with anti rust paint. The iron cabinet shall not be opened with electric (gas) welding, and a hole opener shall be used for opening.
9、配电柜内二层板与进、出线配管位置处理不当,形成配线摆放不整齐,在设备配电柜时应考虑进出线配管管口位置应设置在二层板后边。
9. Improper handling of the position of the second floor board and the inlet and outlet piping inside the distribution cabinet has resulted in uneven wiring arrangement. When installing equipment distribution cabinets, it should be considered that the inlet and outlet piping openings should be placed behind the second floor board.